The microprocessor based manual alarm Control and indication panel is designed to individual zoning the
fire input and evacuated /alert fire in earliest practicable moment with the help 24 V hooter output .
The panel operates on 220 V AC Mains with 24 V DC Battery as a stand by power , The built in circuit
provide constant voltage charging to maintain the battery capacity.

1-Operates on 220 V AC supply.
2-Stand by battery backup with Built in charging.
3-Error free panel status in unambiguous colored LED indication.
4-System on Mains ON battery Low status indication.
5-Low battery visual warning with Audio able tone.
6-Zone wise fire fault Operating indication Facility.
7-Zone ON indication Facility.
8-24 V Hooter Output with silence facility.
9-Manual test facility
10-Rugged CRCA sheet with powder coated finish.
11-Compect size, Sleek Design.
12-Relay Output for associate gadgets.

The enclosure of the panel is constructed by CRCA Sheet with powder-coated finish and its designed to afford
the degree of protection as per IP54 , The 20 mm Knock outs are given for cable entry at the top of the cabinet.
The Panel has a built in battery space for 2Nos of 12 V , 7 AH Batteries.
The front side of the panel consist of the following
1) Control Switches
2) LED Indication

OPERATING VOLTAGE : 24 DC+ 10%
MAINS SUPPLY : 190V AC-240V AC
STAND BY SUPPLY : 24V/4.5Amper
HOOTER OUTPUT : 24V/2Amax
RELAY RATING : 24V/3Amp
POTENTIAL FREE CONTACT : FIRE & FAULT
VOLTAGE CHARGER : 26.6V

 

ONE POWER NORMAL : 15.6MA/Zone
ALARM CURRENT : 35mA /Zone
AC FUSE RATING : 500mA
DC FUSE RATING : 750mA
BATTERY FUSE RATING : 6Amp
WEIGHT : 6 KG APPROX.